Shinyei THT-S. Датчик температуры и влажности воздуха (защищенное исполнение, линейный аналоговый выход)

Производитель: 
Shinyei Technology Co., Ltd (Япония)

Temperatture and Humiidiitty Transmiitttter

Temperature and Humidity recording and controlling at remote locations Model THT-S Series

THT-S Series transmitter has solid, dust and moisture proof bodies for trouble-free use in factories and plants. Temperature and Humidity output signals are independent, loop powered 4 to 20mA for each measurement. So, these units can be easily connected to indicators, recorders and regulators.
High precision enables highly stable indication, recording and controlling of temperature and humidity. Two types, duct and wall mount type, are available.
The model THT-S series is light, compact, rugged and ideally suited to a wide variety of applications recording, controlling or indicating of temperature and humidity are available by using the model THT-S.

Shinyei THT-S. Устройство мониторинга температуры и влажности воздуха (защищенное исполнение, линейный аналоговый выход)

Feature
Wall and duct mount type available.
Interchangeable humidity sensor for replacement.
Applicable for a wide range of industrial applications.
Compact, light and rugged design for various industrial applications.
Durable and reliable humidity sensor for long term use.
Linear 4 to 20mA output signal.

Characteristics Model THT-SW THT-SD

Mounting System Wall Mounting Duct Mounting
Humidity Sensor Shinyei Humidity Sensor HPR-MQ
Temperature Sensor PT 100 Ohm
Operating Temperature Range -20 to 60deg. C (Sensor)
0 to 60deg. C (Electronics)
Operating Humidity Range 95%rh or less
Humidity Measurement Accuracy +/-3%rh (at 25deg. C, 30 - 90%rh)
Temperature Measurement Accuracy +/-0.5deg. C
Temperature & Humidity Output 4 to 20mA for 0 to 100%rh, 0 to 50deg. C
Power supply 12 to 24 VDC
Weight About 300gs.
Housing Material
Body : Polycarbonate
Probe : ABS

Configuration

Shinyei THT-S. Устройство мониторинга температуры и влажности воздуха (защищенное исполнение, линейный аналоговый выход)

Caution for use
! Avoid condensation and drenching.
! Avoid application of the Humidity Sensor in the salt, inorganic gases and organic gases.